Chemtrol Australia Product - LeakDtec® Leak Detection Controllers

Looking for a quote or to discuss your needs?

You can also review the documentation for technical details and purchasing information.

LeakDtec® Leak Detection Controllers

LeakDtec® Leak Detection Controllers

Leak Alarm Controllers for Leak Detection Cable

The Icon Process Controls LeakPro® LeakDtec® controllers watch a run of LDC-G leak detection cable laid along a bund, sump, floor or the space in a double-walled tank, and raise the alarm the moment a conductive liquid such as water, acid or caustic touches it. A relay then stops a pump, closes a valve or signals your controller or BMS.

Three models:

  • LD1C – one zone, with LEDs and a buzzer, 2 A relay
  • LD4C – four zones, four 3 A relays and RS-485 Modbus
  • LDC-M – one zone on a DIN rail, for a control panel

Adjustable Sensitivity

Four sensitivity levels are set by a switch. At the most sensitive, about 1 cm of wetted cable raises the alarm (tested with tap water), so the controller can be set for the liquid on site.

A complete system: controller, LDC-G cable (1, 3, 10 or 30 m, or custom), cable clips and a 24 V DC supply; a ProAlert® 2 adds a red light and a 108 dB alarm. The LD1C and LDC-M relays are rated to 120 V AC: to switch 230 V AC equipment, use the LD4C (250 V AC) or an interposing relay.

LeakDtec Leak Detection Controllers Specifications

ItemLD1CLD4CLDC-M
Zones (cable inputs)141
CableLDC-G (2-wire)LDC-G (2-wire)LDC-G (2-wire)
Relay outputs1 × 2 A (24 V DC / 120 V AC)4 × 3 A (30 V DC / 250 V AC)1 × 2 A (24 V DC / 120 V AC)
ContactsNO or NCNO or NCNO or NC
Communication–RS-485 Modbus–
AlarmLEDs, buzzer with muteLED per zone, reset buttonLED, buzzer with mute
Sensitivity4 levelsAdjustable4 levels
Response time≤ 1 s–≤ 1 s
Power supply9–30 V DC24 V DC9–30 V DC
Operating temperature−40 to +70 °C−20 to +75 °C−40 to +70 °C
ProtectionIP67 (NEMA 4X)IP67 (NEMA 4X)DIN rail, inside a panel
HousingABS / polycarbonateABS / polycarbonate–
Dimensions130 × 80 × 86 mm150 × 150 × 91 mm38 × 84 × 57 mm

Applications

  • Dosing pump skids and chemical bunds
  • The space between the walls of a double-walled tank
  • Sumps and pits
  • Plant rooms and pump rooms
  • Under water tanks, pipework and equipment

Key Features

  • Real-time leak alarm
  • LED indicators and audible alarm
  • Adjustable sensitivity
  • One or four zones
  • Relay outputs, NO or NC
  • RS-485 Modbus (LD4C)
  • IP67 (NEMA 4X) corrosion-resistant enclosure
  • Quick-connect cable glands: no internal wiring