Chemtrol Australia Product - ITC-7200 & ITC-8000 Data Loggers

Looking for a quote or to discuss your needs?

You can also review the documentation for technical details and purchasing information.

ITC-7200 & ITC-8000 Data Loggers

ITC-7200 & ITC-8000 Data Loggers

Multichannel Data Loggers, Displays and Controllers with a Colour Touchscreen

The Icon Process Controls LevelPro® ITC-7200 and ITC-8000 are panel-mounted data loggers that measure, display and record many process signals at once: level, flow, pressure, temperature, pH, ORP and more. Readings are recorded into 1.5 GB of internal memory, from every 0.1 second to every 24 hours, and shown as numbers, bar graphs, needles or trend charts on a colour touchscreen.

The two share the same platform and differ in size:

  • ITC-7200 – 3.5″ colour touchscreen, 96 × 96 mm case, up to 48 analogue inputs
  • ITC-8000 – 5.7″ colour touchscreen, 144 × 144 mm case, up to 72 analogue inputs

Built to Your Inputs

Input, output and communication modules are fitted to suit each site: 4–20 mA and voltage, thermocouple, RTD, counter and flowmeter inputs; 4–20 mA, relay and SSR outputs. RS-485 and a USB port come standard, with Ethernet as an option, and Modbus RTU (master or slave), Modbus TCP and a web server connect it to a PLC, SCADA or your network. The free DAQ Manager software turns the records into graphs, reports and exports.

Typical recording time with 48 channels: about 30 days at one reading a second, 8 months at every 10 seconds, or 4 years at every minute.

ITC-7200 & ITC-8000 Data Loggers Specifications

ItemITC-7200ITC-8000
Display3.5" colour TFT touchscreen5.7" colour TFT touchscreen
Analogue inputs (0/4–20 mA, 0/1–5 V, 0/2–10 V)Up to 48Up to 72
Universal isolated inputsUp to 9Up to 15
Thermocouple / RTD inputsUp to 24 / up to 12Up to 36 / up to 18
Counter and flowmeter inputsUp to 12 counters (5 kHz), 12 digital flowmeters (50 kHz)Up to 12 counters (5 kHz), 12 digital flowmeters (50 kHz)
Digital inputsUp to 49Up to 73
OutputsUp to 8 × 4–20 mA, 16 relays (1 A), 4 relays (5 A), 16 SSRUp to 24 × 4–20 mA, 36 relays (1 A), 18 relays (5 A), 72 SSR
Sensor supply24 V DC, 200 mA24 V DC, 200 mA
Data memory1.5 GB internal1.5 GB internal
Recording interval0.1 s to 24 h0.1 s to 24 h
CommunicationRS-485 and USB standard; Ethernet, extra RS-485 and RS-232 by moduleRS-485 and USB standard; Ethernet, extra RS-485 and RS-232 by module
ProtocolsModbus RTU master or slave, Modbus TCP server, HTTPModbus RTU master or slave, Modbus TCP server, HTTP
Power supply85–260 V AC/DC, or 19–50 V DC / 16–35 V AC85–260 V AC/DC, or 19–50 V DC / 16–35 V AC
Power consumptionTyp. 15 VA, max. 20 VATyp. 25 VA, max. 35 VA
Front protectionIP65 (IP40 with front USB)IP65 (IP40 with front USB)
Case96 × 96 × 100 mm, panel mount144 × 144 × 100 mm, panel mount
Panel cut-out90.5 × 90.5 mm137 × 137 mm
Operating temperature0 to +50 °C (−20 °C option)0 to +50 °C (−20 °C option)

Applications

  • Water and wastewater treatment plants
  • Chemical dosing and tank farm records
  • Cooling water and boiler systems
  • Compliance records for levels, flows and temperatures
  • Control panels and SCADA links

Key Features

  • Colour touchscreen, 3.5″ or 5.7″
  • Up to 48 or 72 inputs
  • 1.5 GB internal recording memory
  • Records every 0.1 s to every 24 h
  • Trends, bar graphs and needles per channel
  • Maths, PID control, timers and profiles
  • Modbus RTU, Modbus TCP and web server
  • Free DAQ Manager PC software
  • Password protected