Looking for a quote or to discuss your needs?
You can also review the documentation for technical details and purchasing information.
ITC-7200 & ITC-8000 Data Loggers
- Product Details
- Specifications
- Applications & Features
ITC-7200 & ITC-8000 Data Loggers
Multichannel Data Loggers, Displays and Controllers with a Colour Touchscreen
The Icon Process Controls LevelPro® ITC-7200 and ITC-8000 are panel-mounted data loggers that measure, display and record many process signals at once: level, flow, pressure, temperature, pH, ORP and more. Readings are recorded into 1.5 GB of internal memory, from every 0.1 second to every 24 hours, and shown as numbers, bar graphs, needles or trend charts on a colour touchscreen.
The two share the same platform and differ in size:
- ITC-7200 – 3.5″ colour touchscreen, 96 × 96 mm case, up to 48 analogue inputs
- ITC-8000 – 5.7″ colour touchscreen, 144 × 144 mm case, up to 72 analogue inputs
Built to Your Inputs
Input, output and communication modules are fitted to suit each site: 4–20 mA and voltage, thermocouple, RTD, counter and flowmeter inputs; 4–20 mA, relay and SSR outputs. RS-485 and a USB port come standard, with Ethernet as an option, and Modbus RTU (master or slave), Modbus TCP and a web server connect it to a PLC, SCADA or your network. The free DAQ Manager software turns the records into graphs, reports and exports.
Typical recording time with 48 channels: about 30 days at one reading a second, 8 months at every 10 seconds, or 4 years at every minute.
ITC-7200 & ITC-8000 Data Loggers Specifications
| Item | ITC-7200 | ITC-8000 |
|---|---|---|
| Display | 3.5" colour TFT touchscreen | 5.7" colour TFT touchscreen |
| Analogue inputs (0/4–20 mA, 0/1–5 V, 0/2–10 V) | Up to 48 | Up to 72 |
| Universal isolated inputs | Up to 9 | Up to 15 |
| Thermocouple / RTD inputs | Up to 24 / up to 12 | Up to 36 / up to 18 |
| Counter and flowmeter inputs | Up to 12 counters (5 kHz), 12 digital flowmeters (50 kHz) | Up to 12 counters (5 kHz), 12 digital flowmeters (50 kHz) |
| Digital inputs | Up to 49 | Up to 73 |
| Outputs | Up to 8 × 4–20 mA, 16 relays (1 A), 4 relays (5 A), 16 SSR | Up to 24 × 4–20 mA, 36 relays (1 A), 18 relays (5 A), 72 SSR |
| Sensor supply | 24 V DC, 200 mA | 24 V DC, 200 mA |
| Data memory | 1.5 GB internal | 1.5 GB internal |
| Recording interval | 0.1 s to 24 h | 0.1 s to 24 h |
| Communication | RS-485 and USB standard; Ethernet, extra RS-485 and RS-232 by module | RS-485 and USB standard; Ethernet, extra RS-485 and RS-232 by module |
| Protocols | Modbus RTU master or slave, Modbus TCP server, HTTP | Modbus RTU master or slave, Modbus TCP server, HTTP |
| Power supply | 85–260 V AC/DC, or 19–50 V DC / 16–35 V AC | 85–260 V AC/DC, or 19–50 V DC / 16–35 V AC |
| Power consumption | Typ. 15 VA, max. 20 VA | Typ. 25 VA, max. 35 VA |
| Front protection | IP65 (IP40 with front USB) | IP65 (IP40 with front USB) |
| Case | 96 × 96 × 100 mm, panel mount | 144 × 144 × 100 mm, panel mount |
| Panel cut-out | 90.5 × 90.5 mm | 137 × 137 mm |
| Operating temperature | 0 to +50 °C (−20 °C option) | 0 to +50 °C (−20 °C option) |
Applications
- Water and wastewater treatment plants
- Chemical dosing and tank farm records
- Cooling water and boiler systems
- Compliance records for levels, flows and temperatures
- Control panels and SCADA links
Key Features
- Colour touchscreen, 3.5″ or 5.7″
- Up to 48 or 72 inputs
- 1.5 GB internal recording memory
- Records every 0.1 s to every 24 h
- Trends, bar graphs and needles per channel
- Maths, PID control, timers and profiles
- Modbus RTU, Modbus TCP and web server
- Free DAQ Manager PC software
- Password protected