CHEMTROL® CT3000 Cooling Tower Controller
Full chemical automation, programmed your way
The CHEMTROL® CT3000 is a fully programmable controller for complete chemical automation of cooling towers, boilers and wastewater: conductivity and ORP as standard, with pH as an option, up to four chemical additives – inhibitors, biocides, dispersants and more – plus water level and influent and effluent pressure.
Its eight-line screen shows every process at a glance, so you can respond quickly to any change. Settings are entered on the 16-key front keypad, and remote operation lets you do the same from your computer or phone.
Standard features
- Conductivity and ORP control, and temperature display
- Four chemical feeds
- Make-up and bleed water meter totalisers
- Automatic probe rinse
- Langelier Saturation Index
- Automatic data logging
- Dedicated alarm relay, to alert a BMS or PLC
Compare the Models
| CHEMTROL® Selection / Features | Cooling tower controllers | Boiler controllers | |||
|---|---|---|---|---|---|
| CT110 | CT3000 | CT6000 | BT110 | BT112 | |
| Control Relay Outputs | 6 | 8 | 14 | 6 | 6 |
| Conductivity display & control | ✓ | ✓ | ✓ | 1 | 2 |
| Temperature display | ✓ | ✓ | ✓ | 1 | 2 |
| pH display & control | OPT | OPT | ✓ | OPT | |
| ORP display & control | ✓ | ✓ | ✓ | ||
| pH/ORP Dynamic Probe Failure Analysis | ✓ | ✓ | ✓ | ||
| Water meter inputs; Makeup, Bleed | 2 | 2 | 2 | ||
| Blowdown Control | 1 | 2 | |||
| Chemical Feed Programs | 3 | 4 | 4 | 3 | 3 |
| Chemical level alarm | ✓ | ✓ | ✓ | ||
| Safety Flow Switch | ✓ | ✓ | ✓ | ||
| Auto Probe Rinse | ✓ | ✓ | |||
| Langelier Saturation Index | ✓ | ✓ | ✓ | ✓ | ✓ |
| Pump Control | OPT | ✓ | |||
| Automatic backwash, filter control | OPT | ✓ | |||
| Automatic Data Logging | ✓ | ✓ | ✓ | ✓ | ✓ |
| Building Management System (BMS) Communications | OPT | OPT | OPT | OPT | OPT |
| Remote monitoring, Web-access | OPT | OPT | ✓ | OPT | OPT |
| Free bromine (ppm) control | OPT | OPT | OPT | ||
| 4–20 mA outputs (OPTION 420M) | OPT | OPT | OPT | ||
| Fluorometer control & display | OPT | OPT | OPT | ||
| Corrosion rate monitoring | OPT | OPT | OPT | ||
| Alarms: Audio, Visual, External | ✓ | ✓ | ✓ | ✓ | ✓ |
| Alarms: Out-of-range, Runtime and Overfeed | ✓ | ✓ | ✓ | ✓ | ✓ |
✓ Included as standard OPT Optional extra, at additional cost
CT3000 Specifications
Control
- Conductivity (TDS) control, with a choice of bleed programs
- ORP monitoring and control of oxidising biocide (chlorine or bromine), to disinfect without overdosing
- Temperature monitoring
- Make-up and bleed water meter totalisers
- Langelier Saturation Index (LSI) calculated automatically, for water balance
Chemical feed
- Up to four chemical additives, such as inhibitors and biocides
- Seven feed programs: manual, cycle timer, bleed-and-feed, bleed-then-feed, percent of make-up flow, daily schedule and two-week schedule
- “Booster” program for a delayed, one-time feed
- Low chemical level alarm, based on each feed outlet’s accumulated run time
Measurement and records
- Dynamic probe testing, with a sensor failure warning
- Automatic probe rinse program, to keep the sensors clean
- Differential signal amplification, for a steady reading
- 1, 2 or 3-point calibration for all sensors
- Automatic data logging – download all your data at any time from the web-server portal
Options
- OPTION pHCT – pH monitoring with automatic acid or base control
- OPTION COMM – remote monitoring and control through the CHEMTROL® web-server and app, by a 4G or 5G router with a SIM card, Ethernet or Wi-Fi; alerts by SMS, email or both
- OPTION LEVCT – water level control, with electronic sensor and fill valve control
- OPTION PSICT – influent and effluent pressure monitoring, with adjustable alarms
- Pump control – with instant and cumulative flow displays
- Automatic filter backwash – filter control with programmable backwash cycles
- Free bromine (ppm) – control on the free bromine level itself, with a ppm sensor
- OPTION 420M – a 4–20 mA electronics module: each sensor listed in the 4–20 mA output menu is sent as a signal to your PLC or SCADA system
- BMS – Modbus or BACnet connection to a building management system
- Fluorometer – inhibitor measurement in ppb, for precise dosing (in-line fluorometer)
- Corrosion monitoring – with adjustable alarms (corrosion monitoring)
CT3000 Installation
The CT3000 is straightforward to install, as the drawings below show. Every controller comes with a detailed installation and operation manual.
For a true water sample and reliable sensor readings, install it with a bypass line assembly manifold.

CT3000 Operation
Everything is set from the front panel. The screen and keypad give direct access to every menu and sub-menu: sensor calibration, set points, alarm levels and the feed programs.
Remote Monitoring & Control
Every CHEMTROL® programmable controller can be monitored and controlled remotely, 24/7. Log in to our web-server from any browser to see the controller’s own display, or use the Chemtrol Live app for Android and Apple.
Open web.chemtrol.com.au on your phone and add it to your home screen. No app store needed.
Change settings in real time, check status reports and trend graphs, and download all your data whenever you need it – for one site or many. See remote monitoring and control.
Alerts that reach the right people
Because the controller is online, its alerts go out by SMS, email or both – to operators, to anyone else who needs them, and to your water treatment technician, so problems are seen and fixed early.
A dedicated alarm relay can also signal any building management system (BMS) or PLC directly.
Connecting the controller
Most sites connect through a 4G or 5G router with a SIM card – we normally work with Telstra, one of Australia’s largest networks. A wired Ethernet cable or Wi-Fi works too. Find out more: web-access options.