IK-1500 Series Smart Sensor Module for AI Critical CDUs

IK-1500 Series Smart Sensor Module for AI Critical CDUs

Complete Coolant Quality Monitoring on One Panel

The Pyxis IK-1500 is a factory-built stainless steel panel that monitors the coolant in a data centre coolant distribution unit (CDU). It measures pH, conductivity, turbidity, glycol concentration and temperature continuously, from one side-stream connection.

Each sensor arrives fitted, wired, tested and calibrated. The panel only needs connecting to the sample line and a 24 V DC supply: plumb, power and go.

The Sensors on the Panel

Two versions are available: the IK-1500, with the RT-100 refractometer and its own display and data logging, and the smaller IK-1500A, with the RT-110L refractometer (no display).

Connects to the Systems You Already Use

Every sensor has its own transmitter with 4–20 mA and RS-485 Modbus outputs, so readings and alarms go straight to the CDU controls, PLC, BMS, EPMS or DCIM platform.

IK-1500 Series Specifications

ItemIK-1500IK-1500A
Part Number4143841179
Glycol SensorRT-100RT-110L
Glycol Sensor Display / Data LoggingIncluded–
pH / Temperature SensorST-710SS
Conductivity / Temperature SensorST-722
Turbidity SensorST-730SS-T (infrared)
Flow CellST-009-03 316L stainless steel three-sensor manifold (included)
RangespH 0–14; conductivity 0.02–10,000 µS/cm; turbidity 0–100 NTU; glycol (ethylene or propylene) 0–100%; refractive index 1.317–1.510; temperature 0–100 °C
PrecisionpH ±0.01 or 1%; conductivity ±0.2 µS/cm or 1% (below 500 µS/cm); turbidity ±0.1 NTU; glycol ±0.1%; refractive index ±0.0001; temperature ±1%
Sample Temperature4 – 49 °C
Maximum Sample Pressure6.9 bar (100 psi)
Sample Inlet / Outlet¼" OD Swagelok® compression
Suggested Flow Rate100 – 2,000 mL/min
Sensor ResponseT95 ≤ 5 seconds; reading every 4 seconds (adjustable)
Sensor Power Supply24 V DC, 1.5 W
Sensor OutputsTwo 4–20 mA and RS-485 Modbus, 8-pin M12 connector
Sensor Body316L stainless steel
Wetted Materials316L SS, fluoroelastomer, EPDM, PEEK, CPVC, POM, quartz, sapphire
Dimensions (H × W × D)700 × 237 × 256 mm507 × 127 × 256 mm
WeightAbout 8 – 12 kg
ProtectionIP67
ApprovalsCE, RoHS
Electrode Service LifeAbout 2 years
WarrantyElectrode 6 months; sensor body 13 months

Ideal for Data Centre Cooling

Liquid-cooled AI and high-performance computing loads depend on coolant that stays within its design chemistry. The IK-1500 watches the key measures together, so a problem shows up early:

  • pH and conductivity show whether corrosion control is working and the inhibitor is still effective in mixed-metal loops.
  • Turbidity gives early warning of particles, corrosion products or biological growth that can foul cold plates, microchannels and heat exchangers.
  • Glycol concentration confirms freeze protection, heat transfer and the correct coolant mix in CDU secondary loops.

Trending all five readings together lets operators link chemistry changes to system events, and act before cooling performance or equipment suffers.

Key Features

  • pH, conductivity, turbidity, glycol and temperature on one panel
  • Factory assembled, tested and calibrated
  • Stainless steel panel with ¼” OD Swagelok® compression connections
  • Every sensor with 4–20 mA and RS-485 Modbus outputs
  • Direct connection to CDU controls, PLC, BMS, EPMS or DCIM
  • Fast response: T95 of 5 seconds or less, readings every 4 seconds
  • Low power: 24 V DC, 1.5 W per sensor
  • Sensors removable for calibration and service
  • IP67 sensors
  • Optional UC-80-PLUS touch screen display and data logger

UC-80-PLUS Display & Data Logger (optional)

A 7-inch colour touch screen that powers the panel and shows live readings, logs data, and handles calibration and sensor diagnostics.

  • Power: 96–260 V AC, 50–60 Hz, 60 W
  • Outputs: 8 × 4–20 mA, RS-485 Modbus RTU and Modbus TCP
  • Inputs: 4 × 4–20 mA, RS-485 Modbus RTU
  • Two 24 V DC relays
  • Stores up to one million readings and events; USB download
  • IP64; 300 × 200 × 190 mm

Replacement Parts and Calibration

  • Replacement ST-710SS, ST-722 and ST-730SS-T sensors
  • Replacement RT-100 or RT-110L refractometer
  • EH-710 replacement electrode head for the ST-710SS
  • ST-009-03 replacement sensor manifold
  • pH calibration solution pack (4.0, 7.0, 10.0)
  • Turbidity standards with glycol: 2, 10 and 100 NTU
  • Conductivity standards: 100 and 1,000 µS/cm