Looking for a quote or to discuss your needs?
You can also review the documentation for technical details and purchasing information.
IK-1600 Series Coolant Chemistry Analyzer for AI Critical CDUs
- Product Details
- Specifications
- Display & Integration
- Video
IK-1600 Series Coolant Chemistry Analyzer for AI Critical CDUs
Complete Coolant Monitoring, with Its Own Touch Screen
The Pyxis IK-1600 is a factory-built stainless steel analyser panel for data centre coolant distribution units (CDUs). It measures pH, conductivity, turbidity, glycol concentration and temperature continuously, and shows them on a 7-inch colour touch screen that also logs the data, handles calibration and raises alarms.
The panel arrives assembled, wired, tested and calibrated: connect the sample line and power, and it is running.
On the Panel
- ST-710SS pH sensor
- ST-722 conductivity sensor
- ST-730SS-T turbidity sensor
- RT-100 Series PRISM™ glycol refractometer
- ST-009-03 three-sensor flow cell
- UC-80-PLUS touch screen display and data logger
Two versions: the IK-1600, with the RT-100 refractometer (its own display and logging), and the IK-1600A, with the RT-110L refractometer. For a panel without the touch screen, see the IK-1500 sensor module.
IK-1600 Series Specifications
| Item | IK-1600 | IK-1600A |
|---|---|---|
| Part Number | 40704 | 40470 |
| Glycol Sensor | RT-100 (with its own display and logging) | RT-110L |
| Other Sensors | ST-710SS pH, ST-722 conductivity, ST-730SS-T turbidity (infrared), on an ST-009-03 flow cell | |
| Ranges | pH 0–14; conductivity 0.02–10,000 µS/cm; turbidity 0–100 NTU; glycol (ethylene or propylene) 0–100%; temperature 0–100 °C | |
| Precision | pH ±0.01 or 1%; conductivity ±0.2 µS/cm or 1% (below 500 µS/cm); turbidity ±0.1 NTU; glycol ±0.1%; temperature ±1% | |
| Display | UC-80-PLUS 7-inch colour touch screen, data logger | |
| Outputs | 8 × 4–20 mA, Modbus RTU and TCP; 2 × 24 V DC relays | |
| Power | 96 – 240 V AC, 50 – 60 Hz | |
| Sample Temperature | 4 – 49 °C | |
| Maximum Sample Pressure | 6.9 bar | |
| Sample Inlet / Outlet | ¼" OD Swagelok® compression | |
| Suggested Flow Rate | 100 – 2,000 mL/min | |
| Sensor Response | T95 ≤ 5 seconds; reading every 4 seconds | |
| Wetted Materials | 316L SS, fluoroelastomer, EPDM, PEEK, CPVC, POM, quartz, sapphire | |
| Panel | Stainless steel; about 8 – 12 kg | |
| Protection | IP67 sensors | |
| Approvals | CE, RoHS | |
| Warranty | Sensors 13 months; electrode 6 months | |
UC-80-PLUS Touch Screen
- 7-inch colour industrial touch screen
- Live readings, data logging, calibration and sensor diagnostics
- Stores up to one million readings and events; USB download
- Two 24 V DC relays for alarms
- Power: 96 – 240 V AC, 50 – 60 Hz, 60 W
Connects to Your Systems
The display passes every reading on through eight 4–20 mA outputs and Modbus RTU and TCP, to the CDU controls, PLC, BMS, EPMS or DCIM platform. Each sensor also has its own 4–20 mA and RS-485 Modbus outputs.
Learn More
How coolant monitoring protects a data centre’s cooling: Data Centre Cooling Monitoring.
Related Products
Product enquiry IK-1600 Series Coolant Chemistry Analyzer for AI Critical CDUs
Prefer to talk? Call 1300 585 820