LDC Leak Detection Cable

LDC Leak Detection Cable

Senses a Leak Anywhere Along Its Length

LeakPro® LDC sensing cable is laid along a floor, bund or containment wherever a leak may run. Liquid anywhere along its length bridges the sensing wires and the controller raises the alarm. The wires are wound in a spiral inside a conductive fluoropolymer jacket and sit 1 mm above the floor, so dirt, metal or debris do not set off false alarms, and the polyethylene cable draws surface liquid onto the wires.

Two cables, not interchangeable:

  • LDC-G – 2-wire cable, for the LeakDtec® controllers, the LDC-M module and the ProAlert® 2 PA223-LD
  • LDC-PC – 4-wire leak-locating cable, for the LeakPoint® controller; acid and alkali resistant

What It Detects

Conductive liquids: water, glycol, brine, acids and caustics. It does not detect oils, fuels or solvents; for those, use the PES photoelectric sensor. The standard LDC-G is chemically resistant but not rated for long exposure to acids or alkalis: for aggressive chemicals, ask us about LDC-PC.

Accessories

  • LDC-L – lead cable from the controller to the sensing cable (LDC-G)
  • LDC-PC-L – lead cable for LDC-PC
  • LDC-TE – end terminal, closes the loop at the end of an LDC-PC run
  • LDC-PC-M / LDC-PC-F – connectors to join LDC-PC lengths
  • CCPP – polypropylene hold-down clips, about every 1.5–2 m
  • CC304 – stainless steel clips

LDC Leak Detection Cable Specifications

ItemLDC-GLDC-PC
Wires24 (leak locating)
Works withLeakDtec® LD1C, LD4C; LDC-M; ProAlert® 2 PA223-LDLeakPoint®
Diameter6 mm6 mm
Cable resistance0.1 Ω/m13 Ω/m
Maximum length150 m150 m
Lengths1, 3, 10, 30 m, or customTo order
JacketPolyethylenePolyethylene
Sensing wiresConductive fluoropolymer jacketConductive fluoropolymer jacket
Flame rating (material)UL 94 V-0UL 94 V-0
Operating temperature−20 to +75 °C−20 to +75 °C
Part numberLDC-G-X (X = length in metres)LDC-PC-X (X = length in metres)

Lay the cable flat, clipped every 1.5–2 m, and do not cut or splice it. Test each run with water when it is installed, and again every year.

Applications

  • Chemical storage tank bunds
  • Dosing pump skids and plant rooms
  • Double-walled tanks and double-contained pipe
  • Floors, raised floors and under equipment
  • Sumps and containment zones

Key Features

  • Senses along its full length, no blind spots
  • No false alarms from dirt, metal or debris
  • Self-wicking polyethylene jacket
  • Fully insulated: no exposed copper
  • Corrosion resistant
  • Custom lengths