LDC Leak Detection Cable
- Product Details
- Specifications
- Applications & Features
LDC Leak Detection Cable
Senses a Leak Anywhere Along Its Length
LeakPro® LDC sensing cable is laid along a floor, bund or containment wherever a leak may run. Liquid anywhere along its length bridges the sensing wires and the controller raises the alarm. The wires are wound in a spiral inside a conductive fluoropolymer jacket and sit 1 mm above the floor, so dirt, metal or debris do not set off false alarms, and the polyethylene cable draws surface liquid onto the wires.
Two cables, not interchangeable:
- LDC-G – 2-wire cable, for the LeakDtec® controllers, the LDC-M module and the ProAlert® 2 PA223-LD
- LDC-PC – 4-wire leak-locating cable, for the LeakPoint® controller; acid and alkali resistant
What It Detects
Conductive liquids: water, glycol, brine, acids and caustics. It does not detect oils, fuels or solvents; for those, use the PES photoelectric sensor. The standard LDC-G is chemically resistant but not rated for long exposure to acids or alkalis: for aggressive chemicals, ask us about LDC-PC.
Accessories
- LDC-L – lead cable from the controller to the sensing cable (LDC-G)
- LDC-PC-L – lead cable for LDC-PC
- LDC-TE – end terminal, closes the loop at the end of an LDC-PC run
- LDC-PC-M / LDC-PC-F – connectors to join LDC-PC lengths
- CCPP – polypropylene hold-down clips, about every 1.5–2 m
- CC304 – stainless steel clips
LDC Leak Detection Cable Specifications
| Item | LDC-G | LDC-PC |
|---|---|---|
| Wires | 2 | 4 (leak locating) |
| Works with | LeakDtec® LD1C, LD4C; LDC-M; ProAlert® 2 PA223-LD | LeakPoint® |
| Diameter | 6 mm | 6 mm |
| Cable resistance | 0.1 Ω/m | 13 Ω/m |
| Maximum length | 150 m | 150 m |
| Lengths | 1, 3, 10, 30 m, or custom | To order |
| Jacket | Polyethylene | Polyethylene |
| Sensing wires | Conductive fluoropolymer jacket | Conductive fluoropolymer jacket |
| Flame rating (material) | UL 94 V-0 | UL 94 V-0 |
| Operating temperature | −20 to +75 °C | −20 to +75 °C |
| Part number | LDC-G-X (X = length in metres) | LDC-PC-X (X = length in metres) |
Lay the cable flat, clipped every 1.5–2 m, and do not cut or splice it. Test each run with water when it is installed, and again every year.
Applications
- Chemical storage tank bunds
- Dosing pump skids and plant rooms
- Double-walled tanks and double-contained pipe
- Floors, raised floors and under equipment
- Sumps and containment zones
Key Features
- Senses along its full length, no blind spots
- No false alarms from dirt, metal or debris
- Self-wicking polyethylene jacket
- Fully insulated: no exposed copper
- Corrosion resistant
- Custom lengths