The Pyxis ST-500 is an inline fluorometer that reads PTSA, the fluorescent tracer added to many cooling water treatment products. Because the tracer goes in at a fixed ratio to the inhibitor, the PTSA reading tells you how much treatment is actually in the system, not just how long the pump has run.

The probe sits in the sample line in its own tee and sends the reading to a controller, PLC or DCS over 4–20 mA or RS-485 Modbus. The controller can then dose to hold the product at its set point as cycles and heat load change. Range is 0 – 300 ppb, accurate to ±1 ppb.

Reads Through Colour and Turbidity

Dirty cooling water scatters and absorbs light, which makes most fluorometers read low. The ST-500 measures the sample’s turbidity and colour at the same time and corrects for them, up to 150 NTU and colour equal to 10 ppm iron. Its flow channel is short and open, so it is quick to clean, and the uPyxis® app tells you when it needs it.

Specifications

ItemST-500
Part Number50661
MeasuresPTSA (pyrenetetrasulfonic acid) fluorescent tracer
Output Scale (4–20 mA)0 – 200 ppb (adjustable in the uPyxis® app)
Maximum Range (via uPyxis®)0 – 300 ppb
Accuracy±1 ppb
Excitation / EmissionLED, 365 nm / 410 nm
CompensationTurbidity up to 150 NTU; colour up to 10 ppm iron
OutputsIsolated 4–20 mA and isolated RS-485 Modbus, 7-pin connector
WirelessBluetooth® with the MA-WB or PowerPACK adapter (uPyxis® app)
Power Supply22 – 26 V DC, 1 W
InstallationST-001 inline tee supplied, ¾" FNPT
Body MaterialCPVC
Operating PressureUp to 6.9 bar (100 psi)
Operating Temperature4 – 49 °C (40 – 120 °F)
Storage Temperature−20 – 60 °C (−4 – 140 °F)
Dimensions172.7 mm long, 36.6 mm diameter (6.8 × 1.44 in)
Weight170 g (0.37 lb)
Cable1.5 m (5 ft) with IP67 connector, plus 0.45 m (1.5 ft) flying lead
ProtectionIP67, dustproof and waterproof
ApprovalsCE, RoHS

The 4–20 mA output is set to 0 – 200 ppb at the factory and can be changed in the uPyxis® app. Pyxis can supply ranges up to 600 ppb on request.

Tracer Control for Cooling Towers

In a traced cooling program, the PTSA level is the treatment level. With the ST-500 feeding the controller, dosing follows the real demand of the tower rather than a timer, so the inhibitor stays inside its band when blowdown, make-up or load changes. It is equally suited to process cooling circuits and other industrial water treated with a PTSA-traced product.

Key Features

  • PTSA from 0 to 300 ppb, ±1 ppb
  • Corrects for turbidity up to 150 NTU and colour up to 10 ppm iron
  • Cleanliness check in the uPyxis® app shows when the probe needs cleaning
  • Short, open flow channel that is quick to clean
  • Isolated 4–20 mA and isolated RS-485 Modbus outputs
  • Calibration over Bluetooth® with the MA-WB or PowerPACK adapter
  • Low power: 22 – 26 V DC, 1 W
  • CPVC body, IP67, supplied with the ST-001 ¾” FNPT inline tee

Installation

The probe fits the ST-001 tee supplied with it, which has two ¾” female NPT ports for an existing sample line. Fit the O-ring, push the probe into the tee and tighten the nut to seal it. Keep the sample below 49 °C and 6.9 bar, and shield an outdoor installation from direct sun and rain.

Cleaning & Calibration

Pyxis recommends a check, clean and calibration once a month; dirtier water needs it more often, clean water less. Soak the lower half of the probe in Pyxis cleaning solution for 30 minutes, brush the quartz channel gently and rinse with distilled water. Calibrate zero with distilled water and the slope with a PTSA standard such as PTSA-100.

A heavily fouled probe reads low, which can lead to overdosing. When the ST-500 controls a dosing pump, set a limit on pump size or run time, or an alarm on the dosing rate.