Active Chlorine ppm Specifications
Spec. | Active chlorine (hypochlorous acid) HOCl | Hot Water Systems | Industrial Water |
---|---|---|---|
Applications | Drinking water Swimming pool water Water of similar quality | Process Water Charged water Polluted water | Process Water Charged water Polluted water |
Measuring range | 0 – 002 ppm (PPMAC002) 0 – 010 ppm (PPMAC010) | 0 – 002 ppm (PPMAC002HP) 0 – 010 ppm (PPMAC010HP) | 0.5 – 100 ppm (PPMAC100) 0.5 – 200 ppm (PPMAC200) |
pH range | 5.5 – 8 pH | 5 – 9 pH | 5.5 – 8 pH |
Temperature range | 5 – 50°C (with temperature compensation) | 40 – 50°C (with temperature compensation) | 5 – 50°C (with temperature compensation) |
Disturbance by other oxidants | Free from isocyanuric acid | Chlorine dioxide (4x) Chlorites Ozone (9x) | Free from isocyanuric acid |
Maximum pressure and flow rate | 3 bar Mini : 20 l/h Maxi : 100 l/h Recommended : 30 l/h | 8 bar Mini : 20 l/h Maxi : 100 l/h Recommended : 30 l/h | 1 bar Mini : 20 l/h Maxi : 100 l/h Recommended : 30 l/h |
Start-up time and final calibration | First calibration after 2 hours After 24 hours | First calibration after 2 hours After 24 hours | First calibration after 2 hours After 24 hours |
Membrane lifetime | Approximately 1 year (depending on water quality/concentration) | Approximately 1 year (depending on water quality/concentration) | Approximately 1 year (depending on water quality/concentration) |
Material and type of protection | PVC black IP 65 | PPE Beige IP 65 | PVC black IP 65 |
Power supply and output signal | 16 – 24 VDC 4-20 mA | 10 – 25 VDC 4-20 mA | 16 – 24 VDC 4-20 mA |