Chemtrol Australia Product - PULSAtron Series T7 Metering Pumps

Looking for a quote or to discuss your needs?

PULSAtron Series T7 Metering Pumps

PULSAtron Series T7 Metering Pumps

Built-in 7-day timer

The PULSAtron Series T7 combines the pump and a 7-day programmable timer in one package, for chemicals dosed on a schedule rather than continuously – such as biocide in an open cooling tower.

Three models, from 1.9 L/h at 7 bar to 4.7 L/h at 7 bar.

Control

  • 7-day programmable timer: up to 8 on/off events a day, in 1-minute steps, on any day
  • Standby and continuous-on modes
  • Stroke length 0–100% (10:1)

Not sure which series suits you? Compare all PULSAtron series, or use our Dosing Pump Selector.

PULSAtron Series T7 models

ModelMax flow (L/h)Max pressure (bar)Tubing connection
LC13BA1.971/4" ID × 3/8" OD
LC14BA3.871/4" ID × 3/8" OD
LC64BA4.771/4" ID × 3/8" OD

Engineering data

  • Pump head: GFPPL, PVC, PVDF or 316 stainless steel
  • Diaphragm: PTFE-faced, CSPE-backed
  • Check valves: Seats and O-rings in PTFE, CSPE or Viton; balls in ceramic, PTFE, 316 stainless steel or Alloy C
  • Fittings: GFPPL, PVC or PVDF
  • Power: 230 VAC or 115 VAC, 50/60 Hz, single phase
  • Approvals: ETL listed, NSF/ANSI 50; PVDF and PVC degassing heads certified to NSF/ANSI/CAN 61 & 372; CE
  • For sodium hypochlorite, choose a PVC liquid end

Cooling Tower Biocide

Biocide is dosed as a shot at set times, not all day. The T7’s timer handles it on its own: up to eight on/off events a day, in one-minute steps, on any day of the week – plus standby and continuous modes. Set the stroke length for the dose and let the timer do the rest.

Key Features

  • Pump and 7-day electronic timer in one package
  • Up to eight on/off events a day, any day of the week
  • Standby and continuous-on modes
  • Repeatable to within ±3% of maximum capacity
  • Isolated from earth ground
  • Few moving parts; wall mountable
  • Leak-free bleed valve, for safe and easy priming
  • Sealless liquid end; rated for continuous duty


PULSAtron Series Metering Pumps – Installation


PULSAtron – How To Change The KOPkit


PULSAtron Series MP 4 20mA Explained