Chemtrol Australia Product - OXIPANEL™ PLUS IK-765SS-BP Oxidizer + pH Analyzer

Looking for a quote or to discuss your needs?

OXIPANEL™ PLUS IK-765SS-BP Oxidizer + pH Analyzer

OXIPANEL™ PLUS IK-765SS-BP Series

The OXIPANEL™ PLUS is a complete oxidiser analyser on one wall panel, ready to plumb in and power up. It measures the oxidiser you dose together with pH, ORP, conductivity and temperature, logs every reading and passes the results to a controller, PLC or SCADA system.

It is made for dirty water such as cooling towers, process water, raw water and treated effluent, where membrane chlorine probes and reagent analysers quickly foul. The panel carries a Pyxis ST-765SS sensor in an FR-300-PLUS brushing flow cell, an FS-100 ultrasonic flow meter with a motorised flow valve, and a UC-80 touch-screen display and data logger.

Choose the version for the oxidiser you need to measure:

  • IK-765SS-FCL-BP – free chlorine
  • IK-765SS-TCL-BP – total chlorine
  • IK-765SS-Br-BP – bromine
  • IK-765SS-CLO-BP – chlorine dioxide

A Brush That Keeps the Sensor Clean

Inside the FR-300-PLUS flow cell, a motor-driven brush sweeps the bare-gold sensor face all the time the sample flows, so scale, slime and oil cannot build up between services. The FS-100 holds the sample at the flow you set, and in automatic mode switches the brush and sensor off if the flow fails.

Specifications

ItemIK-765SS-FCL-BPIK-765SS-TCL-BPIK-765SS-Br-BPIK-765SS-CLO-BP
Part Number41771470044807644376
SensorST-765SS-FCLST-765SS-TCLST-765SS-BrST-765SS-CLO
MeasuresFree chlorineTotal chlorine (reagent-free)BromineChlorine dioxide
Oxidiser Range0.00 – 5.00 ppm
Oxidiser Precision±0.01 mg/L or 1%, pH compensated up to pH 9.0
pH0.00 – 14.00, ±0.01 pH
ORP−1,500 to +1,500 mV, ±1 mV
Conductivity0 – 10,000 µS/cm, ±5%
MeasurementContinuous
Response TimeT95 ≤ 60 s oxidiser; T95 ≤ 5 s pH, ORP and conductivity
SelectivityNot selective: other oxidisers add to the reading
Sample Temperature4 – 49 °C (40 – 120 °F)
Sample Inlet Pressure0.5 – 4.1 bar (7.5 – 60 psi)
Sample Connections⅜" OD tube into ½" NPT port, inlet and outlet
Sample Flow200 – 800 mL/min, set on the FS-100
Flow InterlockAutomatic mode: sensor and brush off below 50 mL/min, back on above 200 mL/min
FS-100 Flow MeterUltrasonic transit-time, 0 – 3,000 mL/min, 1 mL/min or ±2% of reading, 1.44" colour display
Flow ControlMotorised regulating valve, driven 4–20 mA by the FS-100 (PID)
FR-300-PLUS BrushMagnetically coupled motorised brush, 200 rpm; detergent injection port
UC-80 Display4.3" colour resistive touch screen
UC-80 InputRS-485 Modbus RTU
UC-80 OutputsThree 4–20 mA, RS-485 Modbus RTU, Modbus TCP
Relay and ControlOne 24 V DC relay (powered or dry contact, user selected); one analogue PID output
Data Logging128 MB, up to 1 million data and event records; USB host for download and screen upgrade
Remote AccessPyxis 4G CloudLink™ gateway and global SIM included; activated by Pyxis on request
Power Supply96 – 260 V AC, 50 – 60 Hz, 60 W
Relative Humidity20 – 90%, non-condensing
AltitudeBelow 2,000 m (6,561 ft)
Storage Temperature−20 – 70 °C (−4 – 158 °F)
Panel Dimensions450 mm H × 750 mm W × 180 mm D
WeightAbout 10 kg
Sensor Body316L stainless steel
Wetted MaterialsPolycarbonate, 304 and 316 stainless steel, glass, gold, platinum, CPVC, PTFE, POM, ABS, PEEK, PET, NBR
ProtectionIP65 panel and display; IP67 sensors
MethodsUSEPA 334.0 (US); ISO 7393
ApprovalsCE, RoHS, UKCA
Typical LifeElectrode about 2 years; brush 12 – 18 months, depending on the water
WarrantyElectrode 6 months; sensor body and panel 13 months

Spare Parts and Accessories

ItemPart No.
ST-765SS-FCL free chlorine sensor (replacement)53607-NFR
ST-765SS-TCL total chlorine sensor (replacement)53616
ST-765SS-Br bromine sensor (replacement)59643
ST-765SS-CLO chlorine dioxide sensor (replacement)53608-NFR
EH-765 replacement electrode head53061
FR-300-PLUS replacement flow cell50700-A44
FRP-300-01 replacement brush assembly50700-A49
FR-300-03 brush extraction tool23504
FS-100 replacement flow meter54200
Sample flow regulating valve (replacement)21972
UC-80 display and data logger (replacement)14003
pH calibration pack, pH 4, 7 and 1057007
ORP calibration standard, 200 mV57020
Conductivity calibration standard57008
Zero oxidiser calibration standard21002
Probe cleaning kitSER-01

The oxidiser reading is not selective: other oxidisers in the water add to it. The IK-765SS-TCL-BP gives a reagent-free (“virtual”) total chlorine reading; no potassium iodide is added.

Use the OXIPANEL™ PLUS wherever chlorine, bromine or chlorine dioxide must be measured in water that would foul an ordinary probe: cooling towers, food and industrial process water, raw water intakes and treated wastewater. Automatic brushing and flow control mean less time spent cleaning and recalibrating, and a reading the dosing controller can rely on.

Key Features

  • Free chlorine, total chlorine, bromine or chlorine dioxide, 0 – 5 ppm
  • pH, ORP, conductivity and temperature from the same sensor
  • Bare-gold sensor: no membrane, no electrolyte, no reagents
  • Automatic pH and temperature compensation, matching DPD tests up to pH 9
  • Motorised brush flow cell, with a port for injecting cleaning detergent
  • Ultrasonic flow measurement and automatic flow control, 200 – 800 mL/min
  • Sensor and brush stop automatically when the sample flow drops
  • 4.3″ colour touch screen, up to 1 million records, USB download
  • Three 4–20 mA outputs, RS-485 Modbus RTU, Modbus TCP, a relay and a PID output
  • 4G CloudLink™ gateway included, activated by Pyxis on request

Mounting and Plumbing

The panel mounts on a wall: 450 mm high, 750 mm wide, 180 mm deep, about 10 kg. Leave about 0.5 m clear around it for servicing.

  • Sample inlet pressure 0.5 – 4.1 bar (7.5 – 60 psi)
  • Inlet and outlet ⅜” OD tube into ½” NPT ports, or plumb ½” NPT direct
  • Return the outlet to an open sump or a lower-pressure point in the system
  • Set the sample flow, 200 – 800 mL/min, on the FS-100
  • Power 96 – 260 V AC, 50 – 60 Hz, 60 W; mains wiring by a licensed electrician

Maintenance

  • Monthly, or as needed: clean the inlet filter screen, flow cell and electrode head
  • Every 6 months: calibrate pH and ORP, and the oxidiser against a DPD test
  • Every 1 – 2 years: replace the brush and the EH-765 electrode head

After power-up, or after the flow has stopped, the sensor spends 5 minutes preparing its electrode before readings appear.